Installing an energetic fire protection system is no mean investment but all too typically companies are reluctant to take a position the time and money in servicing and testing to ensure that their techniques can continue to guard individuals and property effectively.
Sprinkler systems are the most typical form of active fire protection in offices, outlets and colleges. But they need common servicing to maintain them in full working order.
Whether they contemplate it a low precedence or are unaware of their duties, some users are risking lives and property by not inspecting, testing or maintaining their methods often.
Given the spend on their sprinkler system and the important role it performs within the occasion of a hearth, it is stunning just how many firms wait till they hear the beeping noise from their system alerting them to a problem before they offer service and maintenance their full consideration.
The British Standard BS EN 12845, as incorporated within Part 1 of the Loss Prevention Council Rules for Automatic Sprinkler Installations, makes clear the responsibilities of the user to hold out certain inspections and checks.
Checking and recording the readings on the stress gauges for the valvesets controlling the water to sprinklers for a distribution centre.
Avoiding them may invalidate any certificate of conformity for the set up of their sprinkler or make any insurance warranty void.
There may also be statutory requirements to keep the system serviced such as under the Regulatory Reform (Fire Safety) Order to fulfill a threat evaluation for premises, by which case the proprietor or occupier has a building management responsibility to make sure the system is maintained to the British standard.
The more specialist service and maintenance routines should be carried out, as the usual strictly specifies, beneath contract by both the system installer or an analogous qualified company, who may also provide to hold out some of or all of the user checks as properly.
Choosing a Level four permitted company under the LPC Board’s LPS 1048 Scheme supplies the person with the reassurance that the specialist supplier is certified to service and keep their sprinkler installation to the best quality ranges.
Companies ought to test their sprinkler systems as soon as a week and record the outcomes to ensure that water and air pressures and water levels in the firewater storage tank and the pump priming tank haven’t fallen considerably, reducing their effectiveness in the event of a fire.
They should search the advice of their maintenance provider if any falls are important, or if the water motor alarm fails to sound on check.
Whether they’ve a diesel pump or an electric pump, it is also up to the user to carry out weekly automatic pump starting checks which contain reducing the water strain on the beginning system to simulate automated beginning. They also needs to check fuel and engine lubricating oil levels and the move of cooling water via open circuit cooling systems on their diesel pump.
Immediately after their automated pump starting check, diesel pump users should carry out a diesel engine restarting take a look at by operating the engine for 20 minutes, stopping it after which restarting it using the manual begin button. Again, checks should be made on water levels, oil pressures, and engine temperature and coolant circulate, as nicely as for any leakages.
Checking that the primary valves on the water storage tanks next to the pump home are operating appropriately.
To forestall freezing in winter, the consumer ought to check that heating systems within the sprinkler system are working correctly. If water freezes inside a sprinkler system it can damage the joints between pipes and affect the sprinkler heads too.
BS EN 12845 specifies a month-to-month routine of checking the level and specific gravity of the electrolyte within the cells of all lead acid batteries together with diesel engine starter batteries and those for management panel supplies. If the precise gravity is low and the person has checked that the battery charger is working normally then the time has come to exchange the batteries.
The commonplace also lists a collection of quarterly checks and exams that should be made by a maintenance firm including the cleaning of sprinklers, a quantity of controls and sprayers and the substitute of any with paint deposits or which have turn out to be distorted.
The servicing firm ought to check for corrosion and renew any paintwork, restore tape wrapping, and verify for any illegal electrical earthing connections on pipework and pipe supports.
It should also check the water supply and their alarms, check any secondary electrical supplies from diesel turbines, operate all of the cease valves controlling water flow, and check the move switches to make sure every little thing is in full working order
As nicely as servicing current parts, BS EN 12845 requires the service company to verify the quantity and condition of alternative elements held as spares.
The quarterly necessities also prolong to a evaluation of hazard, which is able to contain the user’s insurance firm checking whether there have been any building modifications which will require a change in design of the sprinkler installation.
On a half-yearly foundation, the servicing company ought to observe the manufacturer’s instructions in exercising the shifting components of any dry alarm valves in dry pipe installations.
Carrying out a weekly run on the diesel set in the pump house.
เพรสเชอร์เกจวัดแรงดันน้ำ , which typically comprise a dry and moist management valve, an accelerator, sprinkler heads and a devoted water provide system, must be charged up with air within the autumn ready for the chilly weather to keep away from freezing, and put in moist mode during spring for the warmer months.
Once a year the service company ought to check that every water supply pump delivers the stress and move rate as stated on the nameplates at full-load condition utilizing the test line linked from the pump delivery pipe.
It should also examine that the automated starting sequence makes six makes an attempt to begin the diesel-engine for the hearth pumps when the fuel supply is turned off and that it switches over to the other duplicate starting batteries after every attempt, and then resets itself automatically.
Ensuring the float valves on the water storage tanks work properly is also on the yearly inspection record. The pump suction strainers and settling chamber and their respective screens additionally must be cleaned the place needed, and the diesel engine serviced in accordance with the manufacturer’s directions.
BS EN 12845 also recommends that sure sprinkler system checks take place although much less regularly. As they require protection from the elements, service suppliers should check the skin of storage and stress tanks for any indicators of corrosion each three years. If there are any such signs, the tank will need to be drained to verify for any internal corrosion, with repainting or repair work carried out if essential.
The provider must also verify and overhaul, or substitute, any water provide cease valves, alarm and non-return valves each three years. While the inside of all storage tanks have to be checked and cleaned or repaired every ten years.
Outside regular inspection visits, it is essential that the top consumer evaluations all their service reviews and follows up any faults immediately with the maintenance firm. A typical contract with a fully certified maintenance provider will embody 24-hour call outs for 365 days a year.
What is especially important is that any remedial work carried out following a service is undertaken by a totally accredited specialist sprinkler specialist and that customers should not try and restore techniques themselves.
A specialist provider corresponding to Argus Fire with LPS 1014 (fire alarm) and LPS 1048 (sprinkler) accreditation will service and maintain not only sprinkler systems but moist and dry risers, hose reels, hearth extinguishers, hydrants and gas suppression systems as part of a maintenance contract and agree a full schedule of inspection, testing and upkeep routines.
For more info, go to www.argusfire.co.uk