A float-based level sensor with a reed chain is a trusted and comparatively economical solution for continuous level measurement in vessels. Users can define its measuring range flexibly within a given range. This short article describes what needs to be taken into account.
With a reed-chain level sensor, the guide tube includes a defined amount of reed contacts, based on the measuring range. They are combined to form a measuring chain. The contacts respond to the magnetic field of the float, which moves within the guide tube based on the liquid level.
Accuracy depends on the length between the contacts
The accuracy of this energy-free level monitoring depends, subsequently, on the distance between your individual contacts: small it is, the more accurate the measurement. pressure gauge in WIKA?s RLT series, for instance, enables measuring ranges with contact distances between 3 and 24 mm. However, a reed chain can’t be stretched across the entire amount of the guide tube. This is because you can find ?dead bands? at both ends of the tube, i.e. sections that the float does not detect because of design constraints (see graphic).
The graph shows the way the maximum possible measuring range (M) with an air-handling series level sensor is defined: Guide tube length (L) minus dead band (T) and 100 % mark (X).
Maximum measuring range isn’t a must
The measuring selection of an even sensor therefore lies between your two dead bands specified in the data sheet. Within this range, it usually is freely defined. However, it is by no means necessary to utilise the maximum possible measuring range in every applications. The exact adaptation of the amount of contacts to the measuring task also offers an economic advantage: The reed chain is among the most expensive components in a level sensor.
Example ? Dry run monitoring
For dry run monitoring in an oil tank of a compressor, for example, only the lower portion of the guide tube is necessary for the measurement. In cases like this, top of the measuring point of the application (100 % mark) is defined correspondingly low. It marks the length to the sealing face of the procedure connection. The measuring range is thus defined by the following equation:
Measuring range length M = guide tube length L ? dead band T ? 100 % mark X
Consequently, the measuring range for detecting a maximum level is set beginning with the sealing face. In this case, the guide tube could be adapted to the length of the measuring range.
Note
Further information on the RLT series level sensors can be found on the WIKA website. Assuming you have any questions, your contact will gladly assist you to.